AC surge protector 60KA lightning arrester spd box electrical power

Share on:


Price:
Price in USD:Details

Quantity:


Product Overview

Description


Product Effects

.jpg 

Product Overviews

_02.jpg

         TRS4 Series surge protective device( hereinafter referred to as SPD) are suitable for AC 50/60Hz, rated voltage up to 380v IT,TT,TN-C, TN-S,TN-C-S and other power supply system, it protect to indirect and direct lightning effect or other transient over voltage. 
    SPD design according with GB18802.1/IEC61643-1 standard.

 

_02.jpg

 

Main technical parameters

Main technical parameters

TRS4-B60

Max continuous operating voltage  Uc(VAC)

420

Voltage protection level  Up(kV)≤

2.2

Max discharge current (8/20μS)  lmax(kA)

60

Nominal discharge current (8/20μS)  ln(kA)

30

Response time ns

<25

Degree of protection

IP20

Operating state/ fault indication

Green/ Red

Remote signal function

Can also picking

Remarks

Other Uc can be customized

SPD according to IEC61643-1/EN61643-1

type2/ Class

 

 

_04.jpg _05.jpg_06.jpg_07.jpg_08.jpg_09.jpg