* Function: AC current measurement
* CT size: Φ68mm
* Range: AC 0.0A~2000A
* Resolution: 0.1A
* Accuracy: ±2.0%FS(50Hz/60Hz; 23℃±2℃)
* Linearity: ≤1.0%
* Phase error: ≤3°(50Hz/60Hz;23℃±2℃)
* Reference load: RL: 0~200mA≤2kΩ;0.2A~2A≤200Ω;2A~20A≤20Ω;20A~200A≤2Ω;200A~2000A≤0.2Ω
* Standard turn ratio: 2400:1 (deuterium ratio can be customized upon request)
* Output method: Current sensing output
* Output interface: 4.0mm double banana plug
* Output line: 2-core shielded cable, length 2m
* Detection method: Clamp CT
* Tested current frequency: 45Hz~60Hz
* Frequency characteristics: 10Hz to 100kHz
* Electric field interference: about 0.3A when the external electric field 100A approaches 10mm
* Wire position: The tested wire is in the center of the jaws
* Line voltage: Test for lines below AC 600V
* Working environment; -20°C~50°C; 80%Rh or less
* Storage environment; -10°C~60°C; 70%Rh or less
* Insulation strength: AC3700V/rms (between core and shell)
* Suitable for safety regulations: IEC1010-1, IEC1010-2-032, Pollution Degree 2, CAT III (600V)
* Weight: 530g
* Appearance size:L x W x H: 185mm×115mm×43mm