Сохранить в закладки 62251005926:
DC motor ULTRA THIN FAN COIL UNIT | |||
Model |
| FLP-50CMD | FLP-60CMD |
Note |
| Two tube type. DC MOTOR.remote control,0-10v light touch screen temperature controller | |
Power supply |
| 220V,50Hz,1Ph | |
Air volume(High speed) | m3/h | 500 | 600 |
Air volume(Medium speed) | m3/h | 380 | 450 |
Air volume(Low speed) | m3/h | 290 | 340 |
Cooling capacity(High speed) | W | 3000 | 3600 |
Btu/h | 10250 | 12300 | |
Cooling capacity(Mid) | W | 2400 | 2880 |
Cooling capacity(Low) | W | 1950 | 2340 |
Heating capacity(1)High speed | W | 4800 | 5750 |
Btu/h | 16400 | 19600 | |
Heating capacity(1)Mid |
| 3840 | 4600 |
Heating capacity(1)Low |
| 2500 | 2990 |
Heating capacity(2) | W | 6150 | 7350 |
Btu/h | 21000 | 25100 | |
Heating capacity(3) | W | 3700 | 4400 |
Btu/h | 12650 | 15000 | |
Noise | dB(A) | 41 | 42 |
Power input | W | 26 | 32 |
Waterflow volume | m3/h | 0.51 | 0.61 |
Pressure dropping | kPa | 10 | 12 |
Water tube connection(inlet) |
| R1/2" | |
Water tube connection(outlet) |
| R1/2" | |
Coil | Type | high efficient copper pipe to wear Hydrophilic aluminum coil | |
Maximum working pressure | Mpa | 1.6 | |
Condensation pipe(diameter) | mm | 21 | |
Net dimension(L*W*H) | mm | 1300*130*681 | 1500*130*681 |
Testing condition:
2-tube system
Cooling
Entering air temperature: Dry bulb 27ºC, Wet bulb 19.5ºC
Entering/out water temperature: 7ºC/ 12℃
Heating(1)
Entering air temperature: 20ºC
Entering water temperature: 60ºC, Same water flow rate as for the cooling
Heating(2)
Entering air temperature: 20ºC
Entering water temperature: 70ºC, Same water flow rate as for the cooling
Heating(3)
Entering air temperature: 20ºC
Entering water temperature: 50ºC, Same water flow rate as for the cooling