Share on (212908361):
Air cooled screw water chiller
1.The main International advanced semi-closed screw compressor in which electric motor and compressor are organically integrated to ensure no leakage of the shaft sealing. Trouble-free operation over 100000hours.
2.Control programs for start and stoppage are applied to double or multiple compressors so as to balance the load and extend the service life of each component.
3.Several refrigeration circuits are provided for double or more compressors. When one circuit needs maintenance, other circuits can work properly as alternative circuits.
4. The compressor is started with unloading and decompression to avoid the impact to the power grid.
5.The vortex and propeller of the compressor is designed to ensure extremely low noise.
6. H/W structural design, favourable thermal radiation.
7.Heat exchanger has the national pressure vessel certificate.
8. 16 years experience
9. Accept orders for special requirements.
10. Use PLC microcomputer control from Germany Siemens LCD touch screen, both English and Chinese human-machine interface.
11. Fluoride-resistant high-performance motor from French.
Accept orders for special requirements

1. R22 (1-2 compressors, 7°C)
| Model[CHYS-**A(H)S3] | 160 | 200 | 240 | 310 | 360 | 400 | 480 | 510 | 550 | 620 | ||
| Cooling Capacity | kW | 161 | 198 | 241 | 311 | 359 | 396 | 481 | 509 | 551 | 621 | |
| ×104 kcal/h | 13.9 | 17 | 20.7 | 26.7 | 30.9 | 34.1 | 41.4 | 43.7 | 47.4 | 53.4 | ||
| Heat Capacity | kW | 178 | 218 | 265 | 242 | 395 | 436 | 529 | 559 | 606 | 683 | |
| ×104 kcal/h | 15.3 | 18.7 | 22.8 | 29.4 | 34 | 37.5 | 45.5 | 48.1 | 52.1 | 58.8 | ||
| 30% Heat-recovery Capacity(kW) | 65 | 78 | 96 | 123 | 142 | 156 | 192 | 201 | 221 | 246 | ||
| Total Refrigeration Input power(kW) | 54.5 | 62.8 | 80 | 99.9 | 115.1 | 125.6 | 160 | 160.8 | 184.5 | 199.8 | ||
| Total Heat Input power(kW) | 54.1 | 62.7 | 79.5 | 99.9 | 114.6 | 125.4 | 159 | 160.7 | 184 | 199.8 | ||
| Compressor | Type | Twin-screw semi-hermetic compressor advanced in the world | ||||||||||
| Quantity | unit | 1 | 1 | 1 | 1 | 2 | 2 | 2 | 2 | 2 | 2 | |
| Refrigeration Input power | kW | 47.7 | 58.2 | 71.1 | 91.1 | 105.9 | 116.4 | 142.2 | 149.3 | 162.2 | 182.2 | |
| Heat Input power | kW | 47 | 58 | 71 | 91 | 105 | 116 | 141 | 149 | 162 | 182 | |
| Energy Adjustment Step for Per Module | 25(start-up)-50-75-100% | |||||||||||
| Refrigerant | Species | —— | R22 | |||||||||
| Control | —— | Thermal expansion valve External Balanced | ||||||||||
| Fans | Quantity | unit | 4 | 4 | 4 | 6 | 8 | 8 | 8 | 10 | 10 | 12 |
| Motor power | kW | 1.1 | 1.4 | 1.46 | 1.47 | 1.1 | 1.4 | 1.46 | 1.47 | 1.47 | 1.47 | |
| Air Side Heat Exchanger | Type | Copper and aluminumfoil finned | ||||||||||
| Water Side Heat Exchanger | Type | Dry shell and tube high efficiency evaporator | ||||||||||
| Water Pipe Connection | mm | DN65 | DN80 | DN80 | DN150 | |||||||
| Water flow | m3/h | 28 | 34 | 41 | 53 | 62 | 68 | 83 | 87 | 94 | 106 | |
| Water Pressure Drop | kPa | 48 | 52 | 55 | 55 | 44 | 44 | 48 | 48 | 52 | 55 | |
| Safe Protection Device | High&Low pressure protection, anti-freezing and anti-heating protection, safety valve, overload protection, incomplete phase protection, opposite phase protection, lacking voltage and over voltage protection, water flow protection, etc | |||||||||||
| Dimensions | Long | mm | 2050 | 2410 | 2850 | 3550 | 4455 | 4815 | 5695 | 5950 | 6395 | 7095 |
| Wide | mm | 2100 | 2100 | 2100 | 2100 | 2100 | 2100 | 2100 | 2100 | 2100 | 2100 | |
| High | mm | 2253 | 2253 | 2253 | 2253 | 2293 | 2293 | 2293 | 2293 | 2293 | 2293 | |
| Noise Value | db(A) | 71 | 71 | 71 | 71 | 75 | 76 | 76 | 77 | 77 | 77 | |
| Total Weight | kg | 1900 | 2090 | 2660 | 3160 | 3990 | 4180 | 5320 | 5250 | 5820 | 6320 | |
| Running Weight | kg | 2000 | 2240 | 2810 | 3310 | 4215 | 4405 | 5545 | 5475 | 6045 | 6545 | |
| 1,The refrigeration conditions for the above table: cold water inlet temperature is 12°C, the outlet temperature is 7°C , and the ambient temperature is 35°C | ||||||||||||
| 2. Power standard: 3N-380V-50Hz; Allow voltage fluctuation ± 10%, allowing phase voltage difference ± 2%; | ||||||||||||
| 3. Noise analysis from the host location for the front of 2m, 1.5m high office, before and after the four-point average of left and right; | ||||||||||||
| Notes:Dimensions for reference only, actual size drawings shall prevail. | ||||||||||||
2. R22 (3-4 compressors, 7°C)
| Model[CHYS-**A(H)S3] | 680 | 750 | 820 | 930 | 1030 | 1100 | 1170 | 1240 | 1340 | 1410 | 1480 | 1550 | ||
| Cooling Capacity | kW | 679 | 751 | 819 | 932 | 1033 | 1102 | 1172 | 1242 | 1343 | 1413 | 1483 | 1553 | |
| ×10³ kcal/h | 584 | 646 | 704 | 801 | 888 | 948 | 1008 | 1068 | 1155 | 1215 | 1275 | 1335 | ||
| Heat Capacity | kW | 747 | 826 | 901 | 1025 | 1136 | 1213 | 1289 | 1366 | 1477 | 1554 | 1631 | 1708 | |
| ×10³ kcal/h | 643 | 710 | 819 | 881 | 977 | 1043 | 1109 | 1175 | 1271 | 1337 | 1403 | 1469 | ||
| 30% Heat-recovery Capacity(kW) | 258 | 299 | 704 | 369 | 409 | 437 | 465 | 493 | 532 | 560 | 588 | 616 | ||
| Total Refrigeration Input power(kW) | 214.2 | 245.3 | 901 | 299.8 | 330.9 | 353.8 | 376.7 | 399.7 | 430.8 | 453.7 | 476.7 | 499.6 | ||
| Total Heat Input power(kW) | 213.1 | 243.8 | 775 | 299.7 | 329.3 | 352.8 | 376.2 | 399.6 | 429.5 | 452.7 | 476.1 | 499.5 | ||
| Compressor | Type | Twin-screw semi-hermetic compressor advanced in the world | ||||||||||||
| Quantity | unit | 3 | 3 | 3 | 3 | 4 | 4 | 4 | 4 | 5 | 5 | 5 | 5 | |
| Refrigeration Input power | kW | 200.4 | 221.8 | 240.4 | 273.3 | 304.4 | 324.4 | 344.4 | 364.4 | 395.5 | 415.5 | 435.5 | 455.5 | |
| Heat Input power | kW | 199 | 220 | 240 | 273 | 303 | 323 | 344 | 364 | 394 | 414 | 435 | 455 | |
| Energy Adjustment Step for Per Module | 25(start up)-50-75-100% | |||||||||||||
| Refrigerant | Species | —— | R22 | |||||||||||
| Control | —— | Thermal expansion valve External Balanced | ||||||||||||
| Fans | Quantity | unit | 12 | 16 | 16 | 18 | 18 | 20 | 22 | 24 | 24 | 26 | 28 | 30 |
| Motor power | kW | 1.4 | 1.47 | 1.47 | 1.47 | 1.47 | 1.47 | 1.47 | 1.47 | 1.47 | 1.47 | 1.47 | 1.47 | |
| Air Side Heat Exchanger | Type | Copper and aluminumfoil finned | ||||||||||||
| Water Side Heat Exchanger | Type | Dry shell and tube high efficiency evaporator | ||||||||||||
| Water Pipe Connection | mm | DN150+DN80 | DN150 X 2 | DN150 x 2+DN80 | DN150 x 2+DN100 | DN150 x 2+DN80 | DN150 x 2+DN100 | |||||||
| Water flow | m3/h | 116 | 129 | 140 | 160 | 177 | 189 | 201 | 213 | 230 | 242 | 254 | 266 | |
| Water Pressure Drop | kPa | 44 | 44 | 48 | 48 | 44 | 44 | 48 | 48 | 44 | 44 | 48 | 48 | |
| Safe Protection Device | High&Low pressure protection, anti-freezing and anti-heating protection, safety valve, overload protection, incomplete phase protection, opposite phase protection, lacking voltage and over voltage protection, water flow protection, etc | |||||||||||||
| Dimensions | Long | mm | 8105 | 9265 | 9505 | 104645 | 12090 | 12790 | 13490 | 14190 | 15640 | 16340 | 17040 | 17740 |
| Wide | mm | 2100 | 2100 | 2100 | 2100 | 2100 | 2100 | 2100 | 2100 | 2100 | 2100 | 2100 | 2100 | |
| High | mm | 2293 | 2293 | 2293 | 2293 | 2293 | 2293 | 2293 | 2293 | 2293 | 2293 | 2293 | 2293 | |
| Noise Value | db(A) | 77 | 78 | 78 | 78 | 78 | 78 | 78 | 78 | 78 | 78 | 79 | 79 | |
| Total Weight | kg | 7410 | 8090 | 8410 | 9480 | 11140 | 11640 | 12140 | 12640 | 14300 | 14800 | 15300 | 15800 | |
| Running Weight | kg | 7635 | 8315 | 8635 | 9705 | 11365 | 11865 | 12365 | 12865 | 14525 | 15025 | 15525 | 16025 | |
| 1,The refrigeration conditions for the above table: cold water inlet temperature is 12°C, the outlet temperature is 7°C , and the ambient temperature is 35°C | ||||||||||||||
| 2. Power standard: 3N-380V-50Hz; Allow voltage fluctuation ± 10%, allowing phase voltage difference ± 2%; | ||||||||||||||
| 3. Noise analysis from the host location for the front of 2m, 1.5m high office, before and after the four-point average of left and right; | ||||||||||||||
| Notes:Dimensions for reference only, actual size drawings shall prevail | ||||||||||||||
3. R407C (1-2 compressors)
| Air Cooled Screw Cold Water Unit Specification Table | ||||||||||||
| Model[CHYS-N**A(H)S3] | 160 | 200 | 240 | 310 | 360 | 400 | 480 | 510 | 550 | 620 | ||
| Cooling Capacity | kW | 158 | 194 | 236 | 304 | 352 | 388 | 472 | 489 | 540 | 609 | |
| ×10³ kcal/h | 136 | 167 | 203 | 262 | 303 | 334 | 406 | 429 | 465 | 523 | ||
| Heating Capacity | kW | 168 | 207 | 251 | 322 | 375 | 414 | 502 | 529 | 573 | 644 | |
| ×10³ kcal/h | 144 | 178 | 216 | 277 | 323 | 356 | 432 | 455 | 493 | 554 | ||
| 30% Heat-recovery Capacity(kW) | 64 | 78 | 95 | 123 | 143 | 157 | 190 | 201 | 218 | 246 | ||
| Total Refrigeration Input power(kW) | 54.9 | 67.2 | 81.1 | 105.3 | 123.3 | 134.5 | 162.3 | 172.8 | 186.5 | 210.6 | ||
| Total Heat Input power(kW) | 55.4 | 68.2 | 81.9 | 107 | 124 | 136.4 | 163.9 | 175.5 | 189 | 214 | ||
| Compressor | Type | Twin-screw semi-hermetic compressor advanced in the world | ||||||||||
| Quantity | unit | 1 | 1 | 1 | 1 | 2 | 2 | 2 | 2 | 2 | 2 | |
| Refrigeration Input power | kW | 50.5 | 61.6 | 75.3 | 96.5 | 112.1 | 123.3 | 150.6 | 158.1 | 171.8 | 192.9 | |
| Heat Input power | kW | 51 | 63 | 76 | 75.3 | 96.5 | 112.1 | 152 | 161 | 174 | 196 | |
| Energy Adjustment Step for Per Module | 25(start up)-50-75-100% | |||||||||||
| Refrigerant | Species | —— | R22 | |||||||||
| Control | —— | Thermal expansion valve External Balanced | ||||||||||
| Fans | Quantity | unit | 4 | 4 | 4 | 6 | 8 | 8 | 8 | 10 | 10 | 12 |
| Motor power | kW | 1.1 | 1.4 | 1.46 | 1.47 | 1.1 | 1.4 | 1.46 | 1.47 | 1.47 | 1.47 | |
| Air Side Heat Exchanger | Type | Copper and aluminumfoil finned | ||||||||||
| Water Side Heat Exchanger | Type | Dry shell and tube high efficiency evaporator | ||||||||||
| Water Pipe Connection | mm | DN80 | DN100 | DN150 | ||||||||
| Water flow | m3/h | 27 | 33 | 40 | 52 | 60 | 67 | 81 | 85 | 93 | 104 | |
| Water Pressure Drop | kPa | 48 | 52 | 55 | 55 | 44 | 44 | 48 | 48 | 52 | 55 | |
| Safe Protection Device | High&Low pressure protection, anti-freezing and anti-heating protection, safety valve, overload protection, incomplete phase protection, opposite phase protection, lacking voltage and over voltage protection, water flow protection, etc | |||||||||||
| Dimensions | Long | mm | 2050 | 2410 | 2850 | 3550 | 4455 | 4815 | 5695 | 5950 | 6395 | 7095 |
| Wide | mm | 2100 | 2100 | 2100 | 2100 | 2100 | 2100 | 2100 | 2100 | 2100 | 2100 | |
| High | mm | 2253 | 2253 | 2253 | 2253 | 2293 | 2293 | 2293 | 2293 | 2293 | 2293 | |
| Noise Value | db(A) | 71 | 71 | 71 | 71 | 75 | 76 | 76 | 77 | 77 | 77 | |
| Total Weight | kg | 1900 | 2090 | 2660 | 3160 | 3990 | 4180 | 5320 | 5250 | 5820 | 6320 | |
| Running Weight | kg | 2000 | 2240 | 2810 | 3310 | 4215 | 4405 | 5545 | 5475 | 6045 | 6545 | |
| 1,The refrigeration conditions for the above table: cold water inlet temperature is 12°C, the outlet temperature is 7°C , and the ambient temperature is 35°C | ||||||||||||
| 2. Power standard: 3N-380V-50Hz; Allow voltage fluctuation ± 10%, allowing phase voltage difference ± 2%; | ||||||||||||
| 3. Noise analysis from the host location for the front of 2m, 1.5m high office, before and after the four-point average of left and right; | ||||||||||||
| Notes:Dimensions for reference only, actual size drawings shall prevail. | ||||||||||||






New products from manufacturers at wholesale prices